Emergency Mixing Valve System with Temperature Override Protection
TA-350-LF
Add to favorites Submit RFQ Now
PDF Catalog Page
PDF Submittal Data Sheet
PDF Operation and Maintenance
PDF Service Record
DURA-trol® solid bimetal thermostat directly linked to valve porting DURA-trol® is highly responsive and cannot be damaged by extremes in temperature Primary valve can be set to the correct temperature for the application. Locking temperature regulator to prevent accidental movement set for 85ºF (29ºC) Primary mixing valve will close down on failure of cold water supply. Primary Mixing Valve with special internal cold water bypass capable of 4 GPM (15 l/min) @ 30 PSI (2.1 Bar) upon failure of hot water supply. Adjustable high temperature limit stop set for 90ºF (32ºC) Dial thermometer (range 0 to 140°F, -10 to 60°C) Straight checkstops on inlets Secondary Thermostatic Control factory locked @ 90°F, 32°C(adjustable from 40°F to 100°F, 4°C to 32°C) to allow cold water to enter the outlet side of the primary mixing valve. Rough bronze finish 

< Go Back

Specification
Inlets 3/4"
Outlet 3/4"
Minimum Flow(GPM) 2
Maximum Flow(GPM) 10
Weight (pounds) 20
Certifications
ASSE 1071
Options
Inlet Thermometers IT