Emergency Mixing Valve System
TM-800
Add to favorites Submit RFQ Now
PDF Catalog Page
PDF Submittal Data Sheet
PDF Operation and Maintenance
DWG CAD Drawing
RFA REVIT Drawing
PDF Maintenance Guide
DURA-trol® solid bimetal thermostat directly linked to valve porting to control the intake of hot and cold water and compensate for supply temperature and pressure fluctuations. DURA-trol® is highly responsive and cannot be damaged by extremes in temperature. Thermostatic Mixing Valve can be set to the correct temperature for the application. Locking temperature regulator to prevent accidental movement set for 85°F (29°C), Recommended Hot Inlet Temperature 140°F. Mixing valve will close down on failure of cold water supply, Mixing Valve with special internal cold water bypass capable of 20 GPM (76 l/min) @ 30 PSI (2.1 Bar) upon failure of hot water supply. Adjustable high temperature limit stop set for 90°F (32°C). Integral wall support, Dial thermometer (range 0 to 140°F, -10 to 60°C), Union angle checkstops with strainers on inlets. Rough bronze finish 
 
This product is available as LEAD FREE. Please see our LEAD FREE section for details and other product offerings.  

< Go Back

Specification
Inlets 1"
Outlet 1 1/4"
Minimum Flow(GPM) 3
Maximum Flow(GPM) 64
Weight (pounds) 20
Certifications
ASSE 1071
Options
Chrome Plated Finish CP
Inlet Thermometers IT