Emergency Mixing Valve System with Temperature Override Protection
TM-850-LF
Add to favorites Submit RFQ Now
PDF Catalog Page
PDF Submittal Data Sheet
PDF Operation and Maintenance
DWG CAD Drawing
PDF Service Record
• DURA-trol® solid bimetal thermostat directly linked to valve porting  
. DURA-trol® is highly responsive and cannot be damaged by extremes in temperature  
• Primary valve can be set to the correct temperature for the application.  
• Locking temperature regulator to prevent accidental movement set for 85ºF (29ºC)  
• Primary mixing valve will close down on failure of cold water supply  
• Primary Mixing Valve with special internal cold water bypass capable of 20 GPM (76 l/min) @ 30 PSI (2.1 Bar) upon failure of hot water supply  
• Adjustable high temperature limit stop set for 90ºF (32ºC)  
• Dial thermometer (range 0 to 140°F, -10 to 60°C)  
• Union Angle checkstops with strainers on inlets  
• Secondary Thermostatic Control factory locked @ 90°F, 32°C(adjustable from 40°F to 100°F, 4°C to 32°C) to allow cold water to enter the outlet side of the Primary mixing valve.  
• Rough bronze finish  

< Go Back

Specification
Inlets 1 1/4"
Outlet 1 1/4"
Minimum Flow(GPM) 3
Maximum Flow(GPM) 64
Weight (pounds) 40
Certifications
ASSE 1071
Options
Inlet Thermometers IT