Ÿ Digital Mixing Valve with integral RTD Sensor

Ÿ Self-Balancing, no need to adjust or balance recirculation

Ÿ Self-Cleaning, daily shuttle sweep keeps shuttle free of debris

Ÿ Valve controls at times of no use: 0.0 GPM*

Ÿ User programmable set point range between 65°F and 180°F

Ÿ Displays outlet temperature

Ÿ Controls water temperature to +/- 2°F during times of low/no system demand

Ÿ Controls water temperature to +/- 2°F in accordance with ASSE 1017

Ÿ Automatic Hot / Cold Water shutoff upon cold / hot water inlet supply failure

Ÿ Alerts user when unit requires maintenance

Ÿ Simple/intuitive user commissioning and setup

Ÿ 3" female NPT inlets, 3" female NPT outlet (76.2mm X 76.2mm)

Ÿ Maximum operating pressure: 200 PSIG (1379 KPA)

Ÿ UL Listed control box and 120V plug in power supply with 6’ cord

Ÿ Available option: Backup Uninterruptable Power Supply. in the event of primary power loss (two hours run time)

*when properly installed near the hot water source with a continuously operating recirculation pump at 5 GPM.

Proton Electronic Mixing Valve - PNV-300-LF-LCV

Downloads
Specification
Inlets 3"
Minimum Flow(GPM) .25
Outlet 3"
Options
Back up Power Supply up to two hours in case of power loss BPS
Megatron Nucleus Installed

Related Products